Your Position: Home > News > technical information

Installation guide of Duct Humidity Sensors

2016/5/10      view:

Installation guide of Duct Humidity Sensors 

Note that humidity sensors are affected by air velocity. The air velocity in the vicinity of the sensor must not exceed 10 m/sec.Precaution: Fit the sensor with a perforated shield or cover (e.g. perforated steel)

Avoid dead-legs. (Supersaturation can occur in areas where there is no air flow.)

Important:When installing sensors in ducts with negative pressure, it is possible for air from an external source to be drawn into the device and the installation hole.(Seal tightly to prevent false readings.)

A test hole must be provided for every humidity sensor (downstream of the sensor). Recommended diameter: 40 mm.

Distance for humidification measurements for BM

BM is the distance between the humidifier and the humidity sensor necessary to allow the air to absorb 100% of the water supplied. The required distance depends on the amount of water supplied, the velocity of the air and the type of humidifier system.
If the humidity sensor is not mounted at the required distance, it will produce a false reading.

Example: Because it is in the wrong position, the sensor here measures only 30% of the water or steam introduced into the system, as only this amount has been fully absorbed in gaseous form into the air. The sensor element will get wet, produce an incorrect reading, and may be damaged.


Distance for adiabatic humidification measurements

This diagram is designed for use in winter, with an absolute humidity content of 1.5 g/kg on the intake side, and a supply air temperature of 18 °C.


Method: Enter the air velocity (in m/s) on the left edge of the diagram (e.g.2.0 m/s). From this point, draw a line to the right, along the line indicating the increase in humidity (example:  x = 10 g/kg).Starting where the two lines intersect, draw a vertical line and read the required distance BM for humidification measurements on the horizontal line at the bottom of the diagram (6.7 m).

Distance BM for humidification measurementswith steam humidifiers

A certain distance is required between humidifier and sensor, so that the air has time to absorb the water (vapour) supplied by the humidifier before the sensor measures the humidity. This distance is marked on the diagram as BM. The minimum distance between the humidifier and the humidity sensor must be equivalent to at least BM.

Method: Enter the increase in humidity in g water/kg air (e.g. 4.5 g/kg) on
the right edge of the diagram.
Draw a horizontal line extending from this point towards the left.
Enter the minimum duct air velocity (in m/s) on the bottom edge of the
diagram (e.g. 1.9 m/s) and draw a vertical line extending upwards from
this point.
From the point of intersection of these two lines, draw a diagonal line extending
upwards and parallel to the existing diagonals. Read the distance,
BM, in metres, from the scale on the edge of the diagram (example 8.5 m).

Average humidity measurement

Locating the humidity sensor in a bypass duct improves the measurement of average, relative or absolute humidity, and should be used:
In cases of temperature or humidity stratification.
Here too, the appropriate distance for humidity measurements, BM, must be maintained.